Emerson MON2020 Gas Grill User Manual


 
Register
Number
Displays the number for the Modbus registers that will be polled by
a connected data acquisition system.
Data Type Describes the type of data that is stored in the register.
Options are:
BOOLEAN. Has two states ON (1) or OFF (0).
INT. 16-bit unsigned integer.
LONG. 32-bit signed integer
Note
If the Modbus data type is Usr Modbus, each long value uses two
registers; if the data type is SIM2251, each long value uses a single
register.
ULONG. 32-bit unsigned integer
FLOAT. 32-bit floating point.
Note
If the Modbus data type is Usr Modbus, each floating point value uses
two registers; if the data type is SIM2251, each floating point value
uses a single register.
Bitmap(INT)
Bitmap(LONG)
SCALED_FP1
...
SCALED_FP32
If one of the scaled floating point options is chosen, the Zero Scale
and Full Scale values for that option will display in the appropriate
column cells.
SIM_2251 registers use only the FLOAT data type.
Variable(s) Displays the variable(s) whose value is to be stored in the register.
To change the variable, see Section 4.11.3.
Access Determines whether the register will be read-only (RD_ONLY) or
read/write (RD_WR).
5. To copy the component settings from a highlighted row and apply them to the next
row, click C + Copy.
This feature also increments the Component value to the next available component
(e.g., incrementing from Ammonia to Benzene), per the GC application. An error
message displays when the last available component is reached.
6. To copy the stream settings from a highlighted row and apply them to the next row,
click S + Copy.
Application
102