12.1 Error Code List
12.1.8 Error code list (6000 to 6999)
6107
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
•Always
• Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
• Confirm the redundant system startup procedure,
and execute a startup again.
RUN:
On
ERR.:
On
CPU Status:
Continue
QnPRH
6108
[TRK. TRANS. ERR.]
• A data error (other than sum value error)
occurred in tracking (data reception).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
•Always
6110
[TRK. SIZE ERROR]
The tracking capacity exceeded the allowed range.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:Tracking capacity excess
error factor
• Individual Information:–
Diagnostic Timing
• When an END instruction executed
Reexamine the tracking capacity.
6111
[TRK. SIZE ERROR]
The control system does not have enough file
register capacity for the file registers specified in
the tracking settings.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• When an END instruction executed
Switch to the file registers of which capacity is
greater than the file registers specified in the
tracking settings.
6112
[TRK. SIZE ERROR]
File registers greater than those of the standby
system were tracked and transmitted from the
control system.
(This can be detected from the standby system of
the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• When an END instruction executed
Switch to the file registers of which capacity is
greater than the file registers specified in the
tracking settings.
Error
Code
(SD0)
Error Contents and Cause Corrective Action