Appendix1 OPERATION PROCESSING TIME
Appendix 1.4 Operation Processing Time of Universal Model QCPU
Category Instruction Condition (Device)
Processing Time (µs)
Q03UD(E)CPU
Q04/
Q06UD(E)HCPU
Q10/Q13/Q20/
Q26UD(E)HCPU
Min. Max. Min. Max. Min. Max.
Application
instruction
RSET
Standard RAM 3.000 6.300 2.700 5.900 2.700 5.900
SRAM card 3.000 6.400 2.600 5.800 2.600 5.800
QDRSET
SRAM card to standard RAM 120.000 134.000 115.000 134.000 115.000 134.000
Standard RAM to SRAM card 533.000 560.000 520.000 553.000 520.000 553.000
QCDSET
SRAM card to standard ROM 306.000 346.000 305.000 346.000 305.000 346.000
Standard ROM to SRAM card 311.000 342.000 300.000 334.000 300.000 334.000
DATERD
––
3.200 5.000 2.500 4.200 2.500 4.200
DATEWR
––
4.900 9.700 4.100 8.900 4.100 8.900
DATE +
No digit increase 5.100 8.000 4.700 6.600 4.700 6.600
Digit increase 5.700 8.000 4.600 6.500 4.600 6.500
DATE -
No digit increase 5.800 8.500 4.600 7.000 4.600 7.000
Digit increase 5.700 7.400 4.600 6.500 4.600 6.500
SECOND
––
2.600 3.900 2.200 3.400 2.200 3.400
HOUR
––
2.900 4.800 2.400 4.300 2.400 4.300
LDDT =
Comparison
of specified
date
In conductive
status
7.400 11.400 6.800 10.900 6.800 10.900
In nonconductive
status
7.400 11.600 6.800 10.900 6.800 10.900
Comparison
of current
date
In conductive
status
5.900 10.000 5.500 9.700 5.500 9.700
In nonconductive
status
5.900 10.100 5.500 9.700 5.500 9.700
ANDDT=
When not executed 0.008 0.038 0.038
Comparison
of specified
date
In conductive
status
7.200 11.400 6.500 10.700 6.500 10.700
In nonconductive
status
7.200 11.400 6.500 10.700 6.500 10.700
Comparison
of current
date
In conductive
status
5.700 9.900 5.300 9.300 5.300 9.300
In nonconductive
status
5.700 9.900 5.300 9.300 5.300 9.300
ORDT=
When not executed 0.008 0.038 0.038
Comparison
of specified
date
In conductive
status
7.400 11.500 6.700 10.800 6.700 10.800
In nonconductive
status
7.400 11.500 6.700 10.800 6.700 10.800
Comparison
of current
date
In conductive
status
5.900 10.000 5.400 9.600 5.400 9.600
In nonconductive
status
5.900 10.000 5.400 9.600 5.400 9.600
LDDT <>
Comparison
of specified
date
In conductive
status
7.400 11.400 6.800 10.900 6.800 10.900
In nonconductive
status
7.400 11.600 6.800 10.900 6.800 10.900
Comparison
of current
date
In conductive
status
5.900 10.000 5.500 9.700 5.500 9.700
In nonconductive
status
5.900 10.100 5.500 9.700 5.500 9.700