Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-31
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2411
[FILE OPE. ERROR]
• The file is the one which cannot be specified by
the sequence program (such as comment file).
• The specified program exists in the program
memory, but has not been registered in the
program setting of the Parameter dialog box.
This error may occur when the ECALL, EFCALL,
PSTOP, PSCAN or POFF instruction is executed.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Program error location
Diagnostic Timing
• When instruction executed
Read the individual information of the error using
the peripheral device, check to be sure that the
program corresponds to the numerical values there
(program location), and correct.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
Qn(H)
QnPH
QnPRH
QnU
2412
[FILE OPE. ERROR]
The SFC program file is one that cannot be
designated by the sequence program.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Program error location
Diagnostic Timing
• When instruction executed
Read the individual information of the error using
the peripheral device, check to be sure that the
program corresponds to the numerical values there
(program location), and correct.
Qn(H)
QnPH
QnPRH
QnU
2413
[FILE OPE. ERROR]
No data has been written to the file designated by
the sequence program.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Program error location
Diagnostic Timing
• When instruction executed
Read the individual information of the error using
the peripheral device, check to be sure that the
program corresponds to the numerical values there
(program location), and correct.
Check to ensure that the designated file has not
been write protected.
Qn(H)
QnPH
QnPRH
2500
[CAN'T EXE. PRG.]
• There is a program file that uses a device that is
out of the range set in the PLC parameter device
setting.
• After the PLC parameter setting is changed, only
the parameter is written into the PLC.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/ STOP RUN
• Read the common information of the error using
the peripheral device, check to be sure that the
parameter device allocation setting and the
program file device allocation correspond to the
numerical values there (file name), and correct if
necessary.
• If PLC parameter device setting is changed,
batch-write the parameter and program file into
the PLC.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
[CAN'T EXE. PRG.]
After the index modification of the PLC parameter is
changed, only the parameter is written to the PLC.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/ STOP RUN
When the index modification of the PLC parameter
is changed, batch-write the parameter and program
file into the PLC.
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)