Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
6-93
GBIN(P),DGBIN(P)
1
2
3
4
4
6
7
8
6.3 Data conversion instructions
6.3.10 Conversion of Gray code to BIN 16 and 32-bit data (GBIN(P),DGBIN(P))
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
Data at when the GBIN instruction was issued is outside the 0 to 32767 range.
(Error code: 4100)
Data at when the DGBIN instruction was issued is outside the 0 to 2147483647 range.
(Error code: 4100)
Program Example
(1) The following program converts the Gray code data at D100 when X10 is ON to BIN data,
and stores the result at D200.
[Ladder Mode] [List Mode]
(2) The following program converts the Gray code data at D10 and D11 to BIN data when X1C
is ON, and stores the result at D0 and D1.
[Ladder Mode] [List Mode]
S
S
Step
Instruction
Device
Step
Instruction
Device