Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-44
3102
[LINK PARA. ERROR]
A CC-Link IE controller network parameter error
was detected.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
• Correct and write the network parameters.
• If the error occurs after correction, it suggests a
hardware fault. (Contact your local Mitsubishi
representative.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)*
7
QnPH*
9
QnPRH*
9
QnU
[LINK PARA. ERROR]
• The network module detected a network
parameter error.
• A MELSECNET/H network parameter error was
detected.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
QCPU
[LINK PARA. ERROR]
The station No. specified in pairing setting are not
correct.
• The stations are not numbered consecutively.
• Pairing setting has not been made for the CPU
module at the normal station.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Refer to the troubleshooting of the network module,
and if the error is due to incorrect pairing setting,
reexamine the pairing setting of the network
parameter.
QnPRH
[LINK PARA. ERROR]
The CC-Link IE controller network module whose
first 5 digits of serial No. is "09041" or earlier is
mounted.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Mount the CC-Link IE controller network module
whose first 5 digits of serial No. is "09042" or later.
QnU
[LINK PARA. ERROR]
Group cyclic function in CC-Link IE controller
network that does not correspond to group cyclic
function is set.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Set group cyclic function in function version D or
later of CC-Link IE controller network.
QnU
*9
[LINK PARA. ERROR]
Paring setting in CC-Link IE controller network
modules installed in CPUs except for redundant
CPUs was performed.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Examine the paring setting for the network
parameter in the control staion.
Q00J/Q00/Q01
Qn(H)
*9
QnPH
*9
QnU
*9
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*7 The module whose first 5 digits of serial No. is "09012" or later.
*9 The module whose first 5 digits of serial No. is "10042" or later.