Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
7-114
CALL(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
The device specified for the argument cannot be secured for the data size.
(Error code: 4101)
Following the execution of the CALL (P) instruction, an END, FEND, GOEND, or STOP
instruction is executed before the execution of the RET instruction.
(Error code: 4211)
An RET instruction is executed prior to the execution of the CALL (P) instruction.
(Error code: 4212)
A 17th nesting level is executed. (Error code: 4213)
There is no subroutine program for the pointer specified in the CALL (P) instruction.
(Error code: 4210)
Program Example
(1) The following program executes a subroutine program with argument when X20 is turned
ON.
[Ladder Mode] [List Mode]
Step
Instruction
Device