Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
6-152
STMR
(3) The timer contact goes ON at the leading edge of the command for the STMR instruction,
and after the trailing edge is reached, the timer coil goes OFF at the trailing edge of the
STMR instruction command.
The timer contact is used by the CPU module system, and cannot be used by the user.
(4) Measurement of the present value of the timer specified by the STMR instruction is
executed regardless of the command ON/OFF status of the STMR instruction.
If the STMR instruction is jumped with the JMP or similar instruction, it will not be possible to
get accurate measurement.
(5) Measurement unit for the timer designated by is identical to the low speed timer.
(6) A value between 0 to 32767 can be set for n.
No operation if n is other than 0 to 32767.
(7) The timer designated by cannot be used by the OUT instruction.
If the STMR instruction and the OUT instruction use the same timer number, accurate
operation will not be conducted.
Operation Error
(1) In the following case, an operation error occurs, the error flag (SM0) turns ON, and an error
code is stored into SD0.
The device specified by exceeds the range of the corresponding device.
(For the Universal model QCPU only.) (Error code: 4101)
Command for
STMR instruction
(Coil)
(Contact)
+0
+1
+2
+3
OFF delay timer
One-shot timer after OFF
One-shot timer after ON
ON delay timer + OFF delay time
r
S
D
S
D
D
D
Setting value
designated by n
Set value
designated by n
Set value
designated by n
Set value
designated by n
D
S
D