Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-30
2401
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation or automatic write to
standard ROM.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/
At writing to progurammable controller
• Check and correct the parameters (boot setting).
• Delete unnecessary files in the program memory.
• Choose "Clear program memory" for boot in the
parameter so that boot is started after the
program memory is cleared.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*3
QnPH
QnPRH
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/
At writing to progurammable controller
QnU
[FILE SET ERROR]
The file specified by parameters cannot be made.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/ At writing to
progurammable controller
• Read the individual information of the error using
the peripheral device, check to be sure that the
parameter drive name and file name correspond
to the numerical values there (parameter
number), and correct.
• Check the space remaining in the memory card.
QCPU
[FILE SET ERROR]
• Although setting is made to use the device data
storage file, there is no empty capacity required
for creating the device data storage file in the
standard ROM.
• When the latch data backup function (to standard
ROM) is used, there is no empty capacity
required for storing backup data in standard
ROM. (The parameter number "FFFF
H
" is
displayed for the error individual information.)
• Standard RAM capacity is insufficient that error
history of the module cannot be stored.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/ At writing to
progurammable controller
Secure the empty capacity of the standard ROM. QnU
2410
[FILE OPE. ERROR]
• The specified program does not exist in the
program memory.
This error may occur when the ECALL, EFCALL,
PSTOP, PSCAN, POFF or PLOW instruction is
executed.
• The specified file does not exist.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Program error location
Diagnostic Timing
• When instruction executed
• Read the individual information of the error using
the peripheral device, check to be sure that the
program corresponds to the numerical values
there (program location), and correct.
Create a file created using parameters, and load
it to the CPU module.
• In case a specified file does not exist, write the
file to a target memory and/or check the file
specified with the instruction again.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
Qn(H)
QnPH
QnPRH
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*3 The function version is B or later.