12-42
3101
[LINK PARA. ERROR]
The link refresh range exceeded the file register
capacity.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• When an END instruction executed
Change the file register file for the one that enables
entire range refresh.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*1
QnPH
QnPRH
QnU
*10
[LINK PARA. ERROR]
• When the station number of the MELSECNET/H
module is 0, the PLC-to-PLC network parameter
has been set.
• When the station number of the MELSECNET/H
module is other than 0, the remote master
parameter setting has been made.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Correct the type or station number of the
MELSECNET/H module in the network parameter
to meet the used system.
Qn(H)
*1
QnPH
QnPRH
[LINK PARA. ERROR]
The refresh parameter for the CC-Link IE controller
network is outside the range.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
• Check the network parameters and mounting
status, and if they differ, match the network
parameters and mounting status.
If any network parameter has been corrected,
write it to the CPU module.
• Confirm the setting of the number of extension
stages of the extension base units.
• Check the connection status of the extension
base units and extension cables.
When the GOT is bus-connected to the main
base unit and extension base units, also check
their connection status.
If the error occurs after the above checks, the
cause is a hardware fault. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
Qn(H)*
7
QnPH*
9
QnPRH*
9
QnU
[LINK PARA. ERROR]
• The network No. specified by a network
parameter is different from that of the actually
mounted network.
• The head I/O No. specified by a network
parameter is different from that of the actually
mounted I/O unit.
• The network class specified by a network
parameter is different from that of the actually
mounted network.
• The network refresh parameter of the
MELSECNET/H, MELSECNET/10 is out of the
specified area.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
QCPU
[LINK PARA. ERROR]
A multi-remote I/O network was configured using a
module that does not support the MELSECNET/H
multi-remote I/O network.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Use a module that supports the MELSECNET/H
multi-remote I/O network.
QnPH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*7 The module whose first 5 digits of serial No. is "09012" or later.
*9 The module whose first 5 digits of serial No. is "10042" or later.
*10 The Universal model QCPU except the Q00UJCPU.