12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2102
[SP. UNIT LAY ERR.]
Seven or more A1SD51S have been installed.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Keep the number of A1SD51S to six or fewer.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
2103
[SP. UNIT LAY ERR.]
• Two or more QI60/A1SI61 modules are mounted
in a single CPU system.
• Two or more QI60/A1SI61 modules are set to the
same control CPU in a multiple CPU system.
• Two or more A1SI61 modules are loaded in a
multiple CPU system.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
• Reduce the number of QI60/A1SI61 modules
mounted in the single CPU system to one.
• Change the number of QI60/A1SI61 modules set
to the same control CPU to only one in the
multiple CPU system.
• Reduce the number of A1SI61 modules to only
one in the multiple CPU system. When using an
interrupt module with each QCPU in a multiple
CPU system, replace it with the QI60. (Use one
A1SI61 module + max. three QI60 modules or
only the QI60 modules.)
Qn(H)
*3
QnPH
[SP. UNIT LAY ERR.]
Two or more QI60, A1SI61 interrupt modules have
been mounted.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Install only 1 QI60, A1SI61 module.
Qn(H)
QnPRH
[SP. UNIT LAY ERR.]
Two or more QI60 modules are mounted.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Reduce the QI60 modules to one.
Q00J/Q00/Q01
*5
[SP. UNIT LAY ERR.]
Two or more QI60 modules where interrupt pointer
setting has not been made are mounted.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
• Reduce the QI60 modules to one.
• Make interrupt pointer setting to the second QI60
module and later.
Q00J/Q00/Q01
*3
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.