Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
7-427
SP.FREAD
1
2
3
4
6
6
7
8
7.18 Other instructions
7.18.13 Reading Data from Designated File (SP.FREAD)
(3) Be sure to use word units to designate the number of request read data ( +2), file position
( +4 and +5), and read data device size ( ).
The following shows how the individual device data is read in binary data reading operation.
(4) When reading binary data
(a) If the extension of the target file is omitted, ".BIN" is used as an extension.
(b) When the designated file does not exist, an error occurs.
(c) If the position specified is greater than the existing file size:
The High Performance model QCPU of which the first 5 digits of the serial number
are "01111" or lower results in an error.
The High Performance model QCPU/Process CPU/Redundant CPU/Universal
model QCPU of which the first 5 digits of the serial number are '01112' or higher will
perform reading at point 0 and will be completed normally.
(5) When reading data after CSV format conversion
(a) The elements in CSV format file (cells for EXCEL) are read by each row. The numerical
value and character strings are converted into binary data and stored in the device.
(b) If the extension is omitted, ".CSV" is used as an extension.
(c) When the designated file does not exist, an error occurs.
(d) The elements designated by the number of request read data ( +2) are read from the
beginning of the file.
When the last data of the file is reached before the specified number of data are read:
The High Performance model QCPU of which the first 5 digits of the serial number
are "01111" or lower results in an error.
The High Performance model QCPU/Process CPU/Redundant CPU/Universal
model QCPU whose the first 5 digits of the serial number are '01112' or higher reads
the data up to the point where the reading is possible.
D0
D0
D0
D1
Location to start reading in the file
Control data
H0000
-
K3
D0+0
D0+1
D0+2
D0+3
D0+4
D0+5
D0+6
D0+7
K1
-
K0
-
Execution/completion type
(Not used)
Number of request read data
(Not used)
Designation of columns
Data type specification
H00
File data (in byte units)
D1+0
H11
H22
H33
H44
H55
H66
H77
H88
H99
H
AA
Data device
D1+1
D1+2
D1+3
K3
H33 22
H55
44
H77
Read data
Total
D0