Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-52
4010
[MISSING END INS.]
There is no END (FEND) instruction in the
program.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
Read the common information of the error using a
peripheral device, check error step corresponding
to its numerical value (program error location), and
correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
4020
[CAN'T SET(P)]
The total number of internal file pointers used by
the program exceeds the number of internal file
pointers set in the parameters.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
Qn(H)
QnPH
QnPRH
QnU
4021
[CAN'T SET(P)]
• The common pointer Nos. assigned to files
overlap.
• The local pointer Nos. assigned to files overlap.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
QCPU
4030
[CAN'T SET(I)]
The allocation pointer Nos. assigned by files
overlap.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
4100
[OPERATION ERROR]
The instruction cannot process the contained data.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
QCPU
[OPERATION ERROR]
Access error of ATA card occurs by
SP.FREAD/SP.FWRITE instructions.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
• Take measurements against noise.
• Reset and restart the CPU module.
When the same error is displayed again, the
ATA card has hardware failure.
(Please consult your local Mitsubishi service
center or representative, explaining a detailed
description of the problem.)
Qn(H)
QnPH
QnPRH
QnU
*11
[OPERATION ERROR]
The file being accessed by other functions with
SP.FWRITE instruction was accessed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
• Stop the file accessed with other functions to
execute SP.FWRITE instruction.
• Stop the access with othrer functions and the
SP.FWRITE instructuion to execute at same
time.
QnU
*11
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*11 The Universal model QCPU except the Q00UJCPU, Q00UCPU, and Q01UCPU.