Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
App-15
8
8
8
8
A
6
7
8
Appendix1 OPERATION PROCESSING TIME
Appendix 1.2 Operation Processing Time of Basic Model QCPU
*1 : The FROM/TO instruction differs in processing time according to the number of slots and the loaded
modules. (The CPU also differs in processing time according to the extension base type.)
Instruction Condition (Device)
Processing Time (µs)
Q00JCPU Q00CPU Q01CPU
COM
––
110 77 72
IX
––
65 54 51
IXEND
––
30 26 25
IXDEV + IXSET
Number of contacts 1 145 120 110
Number of contacts 14 770 630 585
FIFW
FIFWP
Number of data points 0 36 32 28
Number of data points 96 36 32 28
FIFR
FIFRP
Number of data points 1 45 41 36
Number of data points 96 93 82 70
FPOP
FPOPP
Number of data points 1 40 37 32
Number of data points 96 40 37 32
FINS
FINSP
Number of data points 0 53 44 38
Number of data points 96 100 89 76
FDEL
FDELP
Number of data points 1 60 50 43
Number of data points 96 110 95 82
FROM n1 n2 n3
n3 = 1 125 105 93
FROMP n1 n2 n3
*1
n3 = 1000 740 695 685
DFRO n1 n2 n3
n3 = 1 130 110 100
DFROP n1 n2 n3
*1
n3 = 500 745 695 675
TO n1 n2 n3
n3 = 1 120 105 92
TOP n1 n2 n3
*1
n3 = 1000 735 680 645
DTO n1 n2 n3
n3 = 1 130 110 99
DTOP n1 n2 n3
*1
n3 = 500 740 680 640
D
D
D
D
S
S
S
S