Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
7-272
ATAN(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
The contents of the designated device or the result of the addition are not "0", or not within
the following range(For the Universal model QCPU only): (Error code: 4140)
0, 2
-126
| Contents of designated device | < 2
128
The value of the specified device is 0.
*2
(For the High Performance model QCPU, Process CPU, Redundant CPU)
(Error code: 4100)
*2: There are CPU modules that will not result in an operation error if 0 is specified. Refer to 3.2.4 for details.
The result exceeds the following range (Operation results in an overflow)
(For the Universal model QCPU only)
2
128
| Operation result | (Error code: 4141)
The value of the specified device is 0, unnormalized number, nonnumeric, and ± .
(For the Universal model QCPU only) (Error code: 4140)
Program Example
(1) The following program seeks the inverse tangent of the 32-bit floating decimal point real
number at D0 and D1, and outputs the angle to the 4 BCD digits at Y40 to Y4F.
[Ladder Mode]
[List Mode]
[Operations involved when D0 and D1 value is 1]
Calculates an angle (radian value)
by TAN
-1
operation ( )
Converts the radian value
into an angle ( )
Converts the angle in
32-bit floating-point real
number into an integer ( )
Outputs the integer-converted
angle to a display device ( )
1
2
3
4
Step Instruction Device
Conversion to BIN
32-bit floating-point
real number
D21
D20
INT
BCD operation
BCD
ATAN
Conversion to angle
DEG
Y4F
BCD value
0045
Y40
D30
b15 b0
BIN value
45
32-bit floating-point
real number
D1
1
D0
32-bit floating-point
real number
D11
D10
TAN
-1
operation
0
.
785398
45