Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-60
4353
[MULTI-COM.ERROR]
The device which cannot be used for the multiple
CPU high-speed transmission dedicated instruction
specified by the program is specified.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnU
*7
4354
[MULTI-COM.ERROR]
The character string which cannot be handled by
the multiple CPU high-speed transmission
dedicated instruction is specified.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
QnU
*7
4355
[MULTI-COM.ERROR]
The number of read/write data (number of request/
receive data) for the multiple CPU high-speed
transmission dedicated instruction specified by the
program is not valid.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
4400
[SFCP. CODE ERROR]
No SFCP or SFCPEND instruction in SFC
program.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Write the program to the CPU module again using
GX Developer.
Qn(H)
QnPH
QnPRH
4410
[CAN'T SET(BL)]
The block number designated by the SFC program
exceeds the range.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Q00J/Q00/Q01
*2
Qn(H)
QnPH
QnPRH
QnU
4411
[CAN'T SET(BL)]
Block number designations overlap in SFC
program.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
4420
[CAN'T SET(S)]
A step number designated in an SFC program
exceeds the range.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*2 The function version is B or later.
*7 The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.