Special offers from our partners!
Find Replacement BBQ Parts for 20,308 Models. Repair your BBQ today.
12-40
3100
[LINK PARA. ERROR]
In a multiple CPU system, the CC-Link IE controller
network module controlled by another CPU is
specified as the head I/O number of the CC-Link IE
controller network module.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-ON/ At reset/ STOP RUN
• Delete the network parameter of the CC-Link IE
controller network module controlled by another
CPU.
• Change the setting to the head I/O number of the
CC-Link IE controller network module controlled
by host CPU.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*7
QnPH
*9
QnU
[LINK PARA. ERROR]
The network parameter of the CC-Link IE controller
network operating as the normal station is
overwritten to the control station.
Or, the network parameter of the CC-Link IE
controller network operating as the control station is
overwritten to the normal station.
(The network parameter is updated on the module
by resetting.)
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-ON/ At reset/ STOP RUN
Reset the CPU module.
Qn(H)
*7
QnPH
*9
QnPRH
*9
QnU
[LINK PARA. ERROR]
• The number of modules actually mounted is
different from that is set in Network parameter for
MELSECNET/H.
• The head I/O number of the actually mounted
module is different from the one set in the
network parameter of the CC-Link IE controller
network.
• Data cannot be handled in the parameter exists.
• The network type of CC-Link IE controller
network is overwritten during power-on. (When
changing the network type, switch RESET to
RUN.)
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-ON/ At reset/ STOP RUN
• Check the network parameter and actual
mounting status, and if they differ, make them
matched. When network parameters are
modified, write them to the CPU module.
• Check the setting of extension base unit stage
number.
• Check the connection status of extension base
unit and extension cable. When the GOT is bus-
connected to the main base unit or extension
base unit, also check its connection status.
If an error occurs even after performing the
above checks, the hardware may be faulty.
(Contact your local Mitsubishi representative,
explaining a detailed description of the problem.)
[LINK PARA. ERROR]
• The CC-Link IE controller network module is
specified for the head I/O number of network
parameter in the MELSECNET/H.
• The MELSECNET/H module is specified for the
head I/O number of network parameter in the
CC-Link IE controller network.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-ON/ At reset/ STOP RUN
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*7 The module whose first 5 digits of serial No. is "09012" or later.
*9 The module whose first 5 digits of serial No. is "10042" or later.