Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-62
4500
[SFCP. FORMAT ERR.]
The numbers of BLOCK and BEND instructions in
an SFC program are not equal.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Write the program to the CPU module again using
the peripheral device.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
4501
[SFCP. FORMAT ERR.]
The configuration of the STEP* to TRAN* to TSET
to SEND instructions in the SFC program is
incorrect.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
4502
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
• STEPI* instruction does not exist in the block of
the SFC program.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Q00J/Q00/Q01
*2
Qn(H)
QnPH
QnPRH
QnU
4503
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
• The step specified in the TSET instruction does
not exist.
• In jump transition, the host step number was
specified as the destination step number.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
• Write the program to the CPU module again
using GX Developer.
• Read the common information of the error using
GX Developer, and check and correct the error
step corresponding to that value (program error
location).
4504
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
• The step specified in the TAND instruction does
not exist.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• STOP RUN
Write the program to the CPU module again using
GX Developer.
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*2 The function version is B or later.