Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-47
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3106
[LINK PARA. ERROR]
The CC-Link link refresh range exceeded the file
register capacity.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• When an END instruction executed
Change the file register file for the one refresh-
enabled in the whole range.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*1
QnPH
QnPRH
QnU
[LINK PARA. ERROR]
The network refresh parameter for CC-Link is out of
range.
Collateral information
• Common Information:File name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Check the parameter setting. QCPU
[LINK PARA. ERROR]
The setting of the network refresh range crosses
over the boundary between the internal user device
and the extended data register (D) or extended link
register (W).
Collateral information
• Common Information:File name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Set the network refresh range so that it does not
cross over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
QnU
3107
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The set mode is not allowed for the version of the
mounted CC-Link module.
Collateral information
• Common Information:File name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset/STOP RUN
Check the parameter setting. QCPU
3200
[SFC PARA. ERROR]
The parameter setting is illegal.
• Though Block 0 was set to "Automatic start" in
the SFC setting of the PLC parameter dialog box,
Block 0 does not exist.
Collateral information
• Common Information:File name
• Individual Information:Parameter number
Diagnostic Timing
•STOP RUN
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
Q00J/Q00/Q01
*1
QnPH
QnPRH
QnU
3201
[SFC PARA. ERROR]
The block parameter setting is illegal.
Collateral information
• Common Information:File name
• Individual Information:Parameter number
Diagnostic Timing
•STOP RUN
Qn(H)
QnPH
QnPRH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.