12-70
6036
[UNIT LAY. DIFF.]
A difference in the remote I/O configuration of the
MELSECNET/H multiplexed remote I/O network
between the control system and standby system of
a redundant system was detected.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:Module No.
• Individual Information:–
Diagnostic Timing
• Always
Check the network cables of the MELSECNET/H
multiplexed remote I/O network for disconnection.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnPRH
6040
[CARD TYPE DIFF.]
In a redundant system, the memory card
installation status (installed/not installed) differs
between the control system and standby system.
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Match the memory card installation statuses (set/
not set) of the control system and standby system.
6041
[CARD TYPE DIFF.]
In a redundant system, the memory card type
differs between the control system and standby
system.
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Match the memory card types of the control system
and standby system.
6050
[CAN'T EXE. MODE]
The function inexecutable in the debug mode or
operation mode (backup/separate mode) was
executed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• Always
Execute the function executable in the debug mode
or operation mode (backup/separate mode).
RUN:
On
ERR.:
On
CPU Status:
Continue
6060
[CPU MODE DIFF.]
In a redundant system, the operation mode
(backup/separate) differs between the control
system and standby system.
(This can be detected from the standby system of
the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/At tracking cable
connection
Match the operation modes of the control system
and standby system.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU