7-124
ECALL(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
The device specified for the argument cannot be secured for the data size.
(Error code: 4101)
Following the execution of the ECALL (P) instruction, an END, FEND, GOEND, or STOP
instruction is executed before the execution of the RET instruction.
(Error code: 4211)
An RET instruction is executed prior to the execution of the ECALL(P) instruction.
(Error code: 4212)
A 17th nesting level is executed. (Error code: 4213)
The subroutine program of the pointer designated by the ECALL(P) instruction does not
exist. (Error code: 4210)
The designated file does not exist. (Error code: 2410)
The designated file cannot be executed. (Error code: 2411)
Program Example
(1) The following program executes program block P0 of the program A-LINE when X20 is
turned ON.
[Ladder Mode] [List Mode]
[MAIN]
Step
Instruction
Device
[A-LINE]
Step
Instruction
Device