12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3302
[SP. PARA ERROR]
The intelligent function module's refresh parameter
are abnormal.
Collateral information
• Common Information:File name
• Individual Information:Parameter number
*2
Diagnostic Timing
• At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
Check the parameter setting.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
3303
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of another
station.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
• Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
• Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of the
host CPU.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
*10
3400
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
H to 0FF0H.
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
Change the head I/O number of the target module
to be within the 0
H to 0FF0H range.
Qn(H)
*1
QnPH
QnPRH
QnU
*7
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
H to 07E0H.
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
Change the head I/O number of the target module
to be within the 0
H to 07E0H range.
Q02U
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is outside the following range.
• Q00JCPU: 0
H to 1E0H
• Q00CPU/Q01CPU: 0H to 3E0H
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At power ON/At reset/STOP RUN
Change the head I/O number of the target module
of the remote password for the number within the
following range.
•Q00JCPU: 0
H to 1E0H
• Q00CPU/Q01CPU: 0H to 3E0H
Q00J/Q00/Q01
*1
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*2 Parameter No. is the value gained by dividing the head I/O number of parameter in the intelligent function module set by GX Configurator by 10H.
*7 The module whose first 5 digits of serial No. is "09012" or later.