7.6 Structure creation instructions
7.6.10 Select Refresh Instruction (COM)
7.6.10 Select Refresh Instruction (COM)
COM
Refer to Section 7.6.9. for the COM instruction of the following CPU modules.
Basic model QCPU of serial No. 04121 or lower
High Performance model QCPU of serial No. 04011 or lower
Process CPU of serial No. 07031 or lower
Function
(1) When the COM instruction is executed, the following refresh operations can be performed.
I/O refresh
CC-Link refresh
CC-Link IE controller network refresh
MELSECNET/H refresh
Auto refresh of intelligent function modules
Auto refresh using QCPU standard area of multiple CPU system
Reading input/output data of all modules other than the multiple CPU system group
Auto refresh using the multiple CPU high speed transmission area of multiple CPU
system
Communication with peripheral device
Remark
The following processing is performed in communication with peripheral device.
Monitor processing of other station
Read of another intelligent function module buffer memory by the serial
communication module
(2) Turning OFF SM775 refreshes all refresh items except I/O refresh.
The first 5 digits of the serial No. are "04122" or higher.