Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
App-66
Appendix 1.4.2
Processing time of instructions other than subset instruction
The following table shows the processing time of instructions other than subset instructions.
(1) Table of the processing time of instructions other than subset instructions
(a) When using Q00UJCPU, Q00UCPU, Q01UCPU and Q02UCPU
Category Instruction Condition (Device)
Processing Time (µs)
Q00UJCPU Q00UCPU Q01UCPU Q02UCPU
Min. Max. Min. Max. Min. Max. Min. Max.
Sequence
instruction
ANB
ORB
MPS
MRD
MPP
––
0.120 0.080 0.060 0.040
INV
When not executed
0.120 0.080 0.060 0.040
When executed
MEP
MEF
When not executed
0.120 0.080 0.060 0.040
When executed
EGP
EGF
When not executed
0.120 0.080 0.060 0.040
When executed
PLS
––
1.800 1.900 1.800 1.900 1.800 1.900 1.300 1.600
PLF
––
1.800 1.900 1.800 1.900 1.800 1.900 1.600 1.700
FF
When not executed
0.240 0.160 0.120 0.080
When executed
1.700 1.800 1.700 1.800 1.700 1.800 1.200 1.500
DELTA
When not executed
0.240 0.160 0.120 0.080
When executed
4.000 14.700 4.000 14.700 4.000 14.700 2.800 3.600
SFT
When not executed
0.240 0.160 0.120 0.800
When executed
1.800 12.600 1.800 12.600 1.800 12.600 1.600 6.600
MC
––
0.240 0.160 0.120 0.080
MCR
––
0.120 0.080 0.060 0.040
FEND
END
Error check performed
250.000 250.000 250.000 250.000 250.000 250.000 175.000 252.000
No error check performed
250.000 250.000 250.000 250.000 250.000 250.000 175.000 221.000