12.1 Error Code List
12.1.7 Error code list (5000 to 5999)
5010
[PRG. TIME OVER]
The program scan time exceeded the constant
scan setting time specified in the PLC RAS setting
of the PLC parameter.
Collateral information
• Common Information:Time (value set)
• Individual Information:Time (value actually
measured)
Diagnostic Timing
•Always
• Review the constant scan setting time.
• Review the constant scan setting time and low
speed program execution time in the PLC
parameter so that the excess time of constant
scan can be fully secured.
RUN:
On
ERR.:
On
CPU Status:
Continue
Qn(H)
QnPH
QnPRH
QnU
[PRG. TIME OVER]
The low speed program execution time specified in
the PLC RAS setting of the PLC parameter
exceeded the excess time of the constant scan.
Collateral information
• Common Information:Time (value set)
• Individual Information:Time (value actually
measured)
Diagnostic Timing
•Always
Qn(H)
QnPH
QnPRH
[PRG. TIME OVER]
The program scan time exceeded the constant
scan setting time specified in the PLC RAS setting
of the PLC parameter.
Collateral information
• Common Information:Time (value set)
• Individual Information:Time (value actually
measured)
Diagnostic Timing
•Always
Review the constant scan setting time in the PLC
parameter so that the excess time of constant scan
can be fully secured.
Q00J/Q00/Q01
5011
[PRG. TIME OVER]
The scan time of the low speed execution type
program exceeded the low speed execution watch
time specified in the PLC RAS setting of the PLC
parameter dialog box.
Collateral information
• Common Information:Time (value set)
• Individual Information:Time (value actually
measured)
Diagnostic Timing
•Always
Read the individual information of the error using
the peripheral device, check the numerical value
(time) there, and shorten scan time if necessary.
Change the low speed execution watch time in the
PLC RAS setting of the PLC parameter dialog box.
Qn(H)
QnPH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding