12-36
3003
[PARAMETER ERROR]
The automatic refresh range of the multiple CPU
system exceeded the file register capacity.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• When an END instruction executed
Change the file register file for the one refresh-
enabled in the whole range.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*1
QnPH
QnU
*10
[PARAMETER ERROR]
The number of devices set at the PLC parameter
device settings exceeds the possible CPU module
range.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
• Read the individual information of the error using
the peripheral device, check the parameter item
corresponding to the numerical value (parameter
No.), and correct it.
• If the error is still generated following the
correction of the parameter settings, the possible
cause is the memory errorm of the CPU module's
program memory or the memory card. (Contact
your local Mitsubishi representative.)
QCPU
3004
[PARAMETER ERROR]
The parameter file is incorrect.
Alternatively, the contents of the file are not
parameters.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
Check whether the parameter file version
is .QPA, and check the file contents to be
sure they are parameters.
3005
[PARAMETER ERROR]
The contents of the parameter are broken.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power-ON/ At reset/ STOP RUN
• Read the individual information of the error using
the peripheral device, check the parameter item
corresponding to the numerical value (parameter
No.), and correct it.
• Write the modified parameter items to the CPU
module again, and power-on the Programmable
Controller or reset the CPU module.
• When the same error occurs again, the hardware
is faulty. Contact your local Mitsubishi
representative, explaining a detailed description
of the problem.
Qn(H)
*7
QnPH
*9
QnPRH
*9
3006
[PARAMETER ERROR]
• The high speed interrupt is set in a Q02CPU.
• The high speed interrupt is set in a multiple CPU
system.
• The high speed interrupt is set when aQA1S6 B
or QA6 B is used.
• No module is installed at the I/O address
designated by the high speed interrupt.
Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
• Delete the setting of the Q02CPU' s high speed
interrupt. To use high speed interrupts, change
the CPU module to one of the Q02H/Q06H/
Q12H/Q25HCPU.
• To use a multiple CPU system, delete the setting
of the high-speed interrupt. To use high speed
interrupts, change the system to a single CPU
system.
• To use either the QA1S6 B or QA6 B, delete
the setting of the high speed interrupt. To use
high speed interrupts, do not use the QA1S6 B/
QA6 B.
• Re-examine the I/O address designated by the
high speed interrupt setting.
Qn(H)
*4
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*4 The module whose first 5 digits of serial No. is "04012" or later.
*7 The module whose first 5 digits of serial No. is "09012" or later.
*9 The module whose first 5 digits of serial No. is "10042" or later.
*10 The Universal model QCPU except the Q00UJCPU.