[OPERATION ERROR]
• The dedicated instruction was executed to the
module mounted on the extension base unit in
the redundant system.
• The instruction for accessing the intelligent
function module mounted on the extension base
unit from the standby system at separate mode
was executed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
• Delete the dedicated instruction for the module
mounted on the extension base unit.
• Delete the instruction for accessing the intelligent
function module mounted on the extension base
unit from the standby system.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
QnPRH
*6
4130
[OPERATION ERROR]
Instructions to read SFC step comment
(S(P).SFCSCOMR) and SFC transition condition
comment (S(P).SFCTCOMR) are executed for the
comment file in ATA card
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When END/other instruction executed
Target comment file is to be other than the
comment file in ATA card.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
Qn(H)
*4
QnPH
*5
QnPRH
4131
[OPERATION ERROR]
The SFC program is started up by the instruction
while the other SFC program has not yet been
completed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Check the SFC program specified by the
instruction. Or, check the executing status of the
SFC program.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
QnU
4140
[OPERATION ERROR]
Operation where the input data is special value
("-0", unnormalized number, nonnumeric, ) is
performed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check the error step
corresponding to the numerical value (program
error part), and correct it.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
4141
[OPERATION ERROR]
Overflow occurs at operation.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check the error step
corresponding to the numerical value (program
error part), and correct it.
4200
[FOR NEXT ERROR]
No NEXT instruction was executed following the
execution of a FOR instruction.
Alternatively, there are fewer NEXT instructions
than FOR instructions.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*4 The module whose first 5 digits of serial No. is "07012" or later.
*5 The module whose first 5 digits of serial No. is "07032" or later.
*6 The module whose first 5 digits of serial No. is "09012" or later.