Appendix 3 SPECIAL RELAY LIST
*7: The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
(8) Debug
*1: The Universal model QCPU except the Q00UJCPU.
TableApp.3.8 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM796
Block information
using multiple CPU
high-speed
transmission
dedicated instruction
(for CPU No.1)
OFF : Block is secured
ON : Block set by SD796
cannot be secured
• Turns ON when the number of the remaining blocks
of the dedicated instruction transmission area used
for the multiple CPU high-speed transmission
dedicated instruction(target CPU= CPU No.1) is less
than the number of blocks specified by SD796.
Turns ON at instruction execution. Turns OFF when
the empty area exists at END processing.
S (When
instruction/END
processing
executed)
New
QnU
*7
SM797
Block information
using multiple CPU
high-speed
transmission
dedicated instruction
(for CPU No.2)
OFF : Block is secured
ON : Block set by SD797
cannot be secured
• Turns ON when the number of the remaining blocks
of the dedicated instruction transmission area used
for the multiple CPU high-speed transmission
dedicated instruction (target CPU= CPU No.2) is less
than the number of blocks specified by SD797.
Turns ON at instruction execution. Turns OFF when
the empty area exists at END processing.
S (When
instruction/END
processing
executed)
New
SM798
Block information
using multiple CPU
high-speed
transmission
dedicated instruction
(for CPU No.3)
OFF : Block is secured
ON : Block set by SD798
cannot be secured
• Turns ON when the number of the remaining blocks
of the dedicated instruction transmission area used
for the multiple CPU high-speed transmission
dedicated instruction (target CPU= CPU No.3) is less
than the number of blocks specified by SD798.
Turns ON at instruction execution. Turns OFF when
the empty area exists at END processing.
S (When
instruction/END
processing
executed)
New
SM799
Block information
using multiple CPU
high-speed
transmission
dedicated instruction
(for CPU No.4)
OFF : Block is secured
ON : Block set by SD799
cannot be secured
• Turns ON when the number of the remaining blocks
of the dedicated instruction transmission area used
for the multiple CPU high-speed transmission
dedicated instruction(target CPU= CPU No.4) is less
than the number of blocks specified by SD799.
Turns ON at instruction execution. Turns OFF when
the empty area exists at END processing.
S (When
instruction/END
processing
executed)
New
TableApp.3.9 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM800 Trace preparation
OFF : Not ready
ON : Ready
• Switches ON when the trace preparation is
completed
S (Status change) New
Qn(H)
QnPH
QnPRH
QnU
*1
SM801 Trace start
OFF : Suspend
ON : Start
• Trace is started when this relay switches ON.
• Trace is suspended when this relay switches OFF.
(All related special Ms switches OFF.)
U M9047
SM802
Trace execution in
progress
OFF : Suspend
ON : Start
• Switches ON during execution of trace. S (Status change) M9046
SM803 Trace trigger
OFF ON: Start
Trace is triggered when this relay switches from OFF
to ON. (Identical to TRACE instruction execution
status)
U M9044
SM804 After trace trigger
OFF : Not after trigger
ON : After trigger
• Switches ON after trace is triggered. S (Status change) New
SM805 Trace completed
OFF : Not completed
ON : End
• Switches ON at completion of trace S (Status change) M9043
SM826 Trace error
OFF : Normal
ON : Errors
• Switches ON if error occurs during execution of trace S (Status change) New
SM829
Forced registration
specification of trace
setting
ON : Forced registration
enabled
OFF : Forced registration
disabled
• Even when the trace condition or the trigger
condition is established, the sampling trace setting
can be set to the CPU module by turning SM829 ON
and registering the sampling trace setting by GX
Developer.
UNew
QnU