Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-18
2100
[SP. UNIT LAY ERR.]
The slot to which the QI60 is mounted is set to
other than Inteli (intelligent function module) or
Interrupt (interrupt module) in the I/O assignment of
PLC parameter.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Make setting again to match the PLC parameter I/O
assignment with the actual loading status.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*3
QnPH
QnPRH
[SP. UNIT LAY ERR.]
• In the I/O assignment setting of PLC parameter,
Inteli (intelligent function module) was allocated
to an I/O module or vice versa.
• In the I/O assignment setting of PLC parameter,
a module other than CPU (or nothing) was
allocated to the location of a CPU module or vice
versa.
• In the I/O assignment setting of the PLC
parameter, switch setting was made to the
module that has no switch setting.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is less
than the number of points of the mounted
module.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
• Make the PLC parameter’s I/O assignment
setting again so it is consistent with the actual
status of the intelligent function module and the
CPU module.
• Delete the switch setting in the I/O assignment
setting of the PLC parameter.
Qn(H)
QnPH
QnPRH
QnU
[SP. UNIT LAY ERR.]
• In the parameter I/O allocation settings, an Inteli
(intelligent function module) was allocated to a
location reserved for an I/O module or vice versa.
• In the parameter I/O allocation settings, a module
other than CPU (or nothing) was allocated to a
location reserved for a CPU module or vice
versa.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is less
than the number of points of the mounted
module.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Reset the parameter I/O allocation setting to
conform to the actual status of the intelligent
function module and the CPU module.
Q00J/Q00/Q01
2101
[SP. UNIT LAY ERR.]
13 or more A-series special function modules
(except for the A1SI61) that can initiate an interrupt
to the CPU module have been installed.
Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
Diagnostic Timing
• At power ON/At reset
Reduce the A series special function modules
(except the A1SI61) that can make an interrupt
start to the CPU module to 12 or less.
Qn(H)
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.