Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
12-72
6102
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• Always
• Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
• Confirm the redundant system startup procedure,
and execute a startup again.
RUN:
On
ERR.:
On
CPU Status:
Continue
QnPRH
6103
[TRK. TRANS. ERR.]
• A data error (other than sum value error)
occurred in tracking (data reception).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• Always
6105
[TRK. TRANS. ERR.]
• An error (e.g. retry limit exceeded) occurred in
tracking (data transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:Tracking transmission data
classification
• Individual Information:–
Diagnostic Timing
• Always
6106
[TRK. TRANS. ERR.]
• A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
• Common Information:Tracking transmission data
classification
• Individual Information:–
Diagnostic Timing
• Always
• Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
• Confirm the redundant system startup procedure,
and execute a startup again.
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU