Mitsubishi Electronics QSERIES Smoker User Manual


  Open as PDF
of 1204
 
7-252
SIND(P)
7.12.2 SIN operation on floating-point data (Double precision)
(SIND(P))
SIND(P)
Function
(1) The SIN (sine) value of the angle specified by is calculated and its result is stored into the
device specified by .
(2) Angles designated at are set in radian units (degrees / 180).
For conversion between degrees and radian values, see the RADD and DEGD instructions.
(3) When the operation results in -0 or an underflow, the result is processed as 0.
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
The value of the specified device is not in the following range: (Error code: 4140)
0,2
-1022
| value of specified device | < 2
1024
The value of the designated device is 0. (Error code: 4140)
The result exceeds the following range (Operation results in an overflow):
2
1024
| Operation result | (Error code: 4141)
: Angle data of which the SIN (sine) value is obtained or head number of the devices where the angle data is
stored (real number)
: Head number of the devices where the operation result will be stored (real number)
Setting
Data
Internal Devices
R, ZR
J\
U\G
Zn
Constants
E
Other
Bit Word Bit Word
–– –– ––
–– –– –– ––
Universal
Basic
Process
High
performance
Redundant
SINDP
SIND
SINDP
SIND S D
S D
Command
Command
S
D
S
D
S
D
SIN (
)
+3
64-bit floating-point
real number
S
+2
S
S
+1
S
+3
64-bit floating-point
real number
D
+2
D
D
+1
D
S