Liebert iCOM
®
Control
91 Liebert
®
CRV
Figure 84 System/Network setup parameters Unit - Page 2
Monitoring Protocol—This parameter selects the monitoring protocol. Velocity V3 is the factory
default which will provide communications to the Liebert IntelliSlot
®
housing. iGMNet will activate
the 77/78 terminals for communications to the Liebert SiteLink
®
(-E). Hironet is used only on HPM
units.
IP Address—This parameter contains the network address of the display. This address must be
unique to every other device on the network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—This parameter is a unique identifier for each unit on the network. Display addresses
range from 33 to 64. Each display on the U2U network must have a different U2U address.
U2U Group—This parameter is used to create zones or groups within a U2U network. Once a group
number is selected the display will only see other devices with the same group number. The group
number can be changed to view other devices in different groups.
Bootloader Variables—This parameter indicates if there has been a change to the boot loader since
it was last loaded. This parameter should only be activated by an authorized service person.
Static RAM
Attention: any changes done on these parameters
must befollowed by a 'Save+Reboot' command.
S834
S835
S836
S837
S838
S839
S840
S841
S842
S843
S844
PASSWORD (Actual Level 0) ????
Monitoring Protocol Velocity V4
IP Address 10.203.062.178
Netmask 255.255.255.192
Gateway 10.203.062.129
MAC 00:00:68:1E:2D:16
U2U Protocol GBP
U2U Address 1
U2U Group 13
Bootloader Variables OK No
Static RAM OK No
SYSTEM / NETWORK SETUP (page 2 of 2) UNIT 01