Liebert iCOM
®
Control
73 Liebert
®
CRV
Figure 61 Standby settings / lead-lag parameters screen
Number of Standby Units—This parameter selects the number of units that will be in Standby
mode. When a unit is in standby mode the fan will be off and no cooling will be provided.
Rotation Frequency—This parameter controls when a rotation will occur between the standby
units and the operating units within a network.
Rotate at (hour)—This parameter sets the hour of the rotation
Rotate at (minute)—This parameter sets the minute of the rotation
Rotate by—This parameter determines the number of positions to rotate by. Example: If there are 6
units in a unit to unit network and units 1, 3 & 5 are in standby and this parameter is set to “1” then
at the next rotation units 2, 4,& 6 will be placed into standby and 1, 3 & 5 will become operational.
Perform one Rotation—This parameter will manually force a single rotation between units.
Cascade Units—This parameter when set allows units to activate from Standby mode if the room
temperature is unable to be maintained by the non-standby units. If yes is selected then the cascade
units can perform all functions when activated from standby. This parameter can also be set for
Cooling Only or Cool / Heat only.
Start all Standby Units by HT—This parameter activates all units to cool when a High
Temperature alarm occurs.
See 3.9.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
S501
S502
S503
S504
S505
S506
S507
S508
S509
S510
S511
PASSWORD (Actual Level 0) ????
Number of Standby Units 0
Rotation Frequency
Rotate at (hour)
Rotate at (minute)
Rotate by
Perform one Rotation
Cascade Units
Start all Standby Units by HT
STANDBY SETTINGS/LEAD-LAG SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then