Liebert iCOM
®
Control
Liebert
®
CRV
86
Figure 77 Sensor calibration / setup parameters - Page 1
Return Temperature—This parameter adjusts the return temperature reading from the actual
sensor to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Temperature—This parameter shows the adjusted temperature value of the
return sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
Return Humidity—This parameter adjusts the return humidity reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Humidity—This parameter shows the adjusted humidity value of the return
sensor. This value is the actual sensor reading (+ or -) the offset “Return Humidity”.
Digiscroll 1 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
Calibrated Digiscroll 1 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Figure 78 Sensor calibration / setup parameters - Page 2
to change parameter
for next/previous unit
to select parameter
to confirm
then
S601
S602
S603
S604
S605
U606
S607
S608
S609
S610
S611
PASSWORD Actual Level 0) ????
Return Temperature +0°F
Calibrated Return Temperature 77°F
Return Humidity +0.0%
Calibrated Return Humidity 26.0%
Digiscroll 1 NTC +0°F
Calibrated Digiscroll 1 NTC 200°F
SENSOR CALIBRATION/SETUP (page 1 of 4) UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622
PASSWORD Actual Level 0) ????
Return T Sensor PTC or NTC NTC
Return T Sensor +0°F
Calibrated Return T Sensor °F
Supply T Sensor PTC or NTC NTC
Supply T Sensor +1°F
Calibrated Supply T Sensor 75°F
CW T Sensor °F
Calibrated CW T Sensor °F
SENSOR CALIBRATION/SETUP (page 2 of 4) UNIT 01