Figure 80 Sensor calibration / setup parameters - Page 4
This unit can be equipped with a total of 20 rack sensor readings or 10 2T temperature sensor
modules. This menu provides the ability to calibrated by entering a negative or positive offset. The
calibrated reading is displayed in the far right column. If a value is not shown in the far right column,
then the sensor is either not setup correctly or is not connected.
Figure 81 System / network setup parameters—System - Page 1
Number of Connected Units—This parameter sets the number of units that will be viewable from
the large display and will participate on the unit to unit network.
Teamwork Mode—This parameter selects which teamwork mode to use within a selected group.
Teamwork modes are described in section 4.0 of this manual.
Teamwork Mode 1 based on
Configuration Safe—This parameter saves or loads configuration settings for the display that have
been modified from the factory defaults to an internal file that can be downloaded / uploaded using
the Liebert iCOM
®
Service Tool. Selecting “Save” will write the settings to the internal storage file
and selecting “Load” will write the settings from the internal storage file to the application software.
The internal file is updated every 12 hours automatically.
to change parameter
for next/previous unit
to select parameter
to confirm
then
S634
S635
S636
S637
S638
S639
S640
S641
S642
S643
S644
PASSWORD Actual Level 0) ????
Rack Temperature Sensor 1B °F 77°F
Rack Temperature Sensor 2B °F 78°F
Rack Temperature Sensor 3B °F 77°F
Rack Temperature Sensor 4B °F 77°F
Rack Temperature Sensor 5B °F 78°F
Rack Temperature Sensor 6B +0°F °F
Rack Temperature Sensor 7B +0°F °F
Rack Temperature Sensor 8B +0°F °F
Rack Temperature Sensor 9B +0°F °F
Rack Temperature Sensor 10B +0°F °F
SENSOR CALIBRATION/SETUP (page 4 of 4) UNIT 01
S801
S802
S803
S804
S805
S806
S807
S808
S809
S810
S811
PASSWORD (Actual Level 0) ????
Number of Connected Units 1
Teamwork Mode No
Teamwork Mode 1 based on
Configuration Safe OK No
Network Safe OK No
SW Version CRB 2.00.006.STD
SYSTEM / NETWORK SETUP (page 1 of 2) SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then