Liebert iCOM
®
Control
77 Liebert
®
CRV
Figure 65 Wellness electric heater 1 settings parameters screen - Page 4
Number of Starts—This parameter shows the number of starts for the unit’s reheats.
Run Hours—This parameter shows the number of run hours for the unit’s reheats.
Average Run Time—This parameter displays the average run time of the unit’s reheats.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of HP Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s reheats.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s reheats. The
unit will always take the value from the worst component for the next maintenance indication.
S034
S035
S036
S037
S038
S039
S040
S041
S042
S043
S044
PASSWORD (Actual Level 0) ????
Number of Starts 0
Run Hours 0hrs
Average Run Time 0min
Starts per Day Best 24
Starts per Day Worst 240
Number of HP Alarms 0
Actual Bonus 0
WELLNESS el heater 1 settings (page 4 of 5) UNIT 1
to change parameter
for next/previous unit
to select parameter
to confirm
then
Screen displayed
only if unit is
equipped with
electric heater