Liebert iCOM
®
Control
Liebert
®
CRV
76
Figure 64 Wellness compressor 1 settings parameters screen - Page 3
Number of Starts—This parameter shows the number of starts for the unit’s compressor.
Run Hours—This parameter shows the number of run hours for the unit’s compressor.
Average Run Time—This parameter displays the average run time of the unit’s compressor.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of HP Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s compressor.
Number of LP Alarms—This parameter displays the number of low pressure alarms that have
occurred with the unit’s compressor.
Number of OL Alarms—This parameter displays the number of overload alarms that have occurred
with the unit’s compressor.
Number of DS HT Alarms—This parameter displays the number of Digital Scroll High
Temperature alarms that have occurred with the unit’s compressor.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s compressor.
The unit will always take the value from the worst component for the next maintenance indication.
S023
S024
S025
S026
S027
S028
S029
S030
S031
S032
S033
PASSWORD (Actual Level 0) ????
Number of Starts 22
Run Hours 3374hrs
Average Run Time 9201 min
Starts per Day Best 12
Starts per Day Worst 240
Number of HP Alarms 0
Number of LP Alarms 0
Number of OL Alarms 0
Number of DS HT Alarms 0
Actual Bonus 0
WELLNESS compressor1 settings (page 3 of 5) UNIT 1