Refrigerant Connections
19 Liebert
®
CRV
6.1 Piping Guidelines—Air-Cooled Units
Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant
piping is in place, ready for connection to the unit and condenser
Use copper piping with high temperature brazed joints
Isolate piping from building using vibration-isolating supports
Refer to Tables 7 through 10 for piping sizes
Refer to condenser installation manual for charging information
Install traps on hot gas (discharge) lines at the base of vertical risers and every 15 feet (4.6m) of
vertical rise.
See Table 6 for the allowable elevation difference between the condenser and the Liebert CRV.
Consult factory if piping run exceeds 300 feet (91m) equivalent length
Keep piping clean and dry, especially on units with R-410A refrigerant
Avoid piping runs through noise-sensitive areas
Do not run piping directly in front of airstream of any air conditioner
Refrigerant oil – do not mix oil types
Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
6.2 Refrigerant Piping—Air-Cooled Models
Figure 14 Top refrigerant piping connections
Figure 15 Bottom refrigerant piping connections
If using bottom
connections, cut
the pipes just
below the black
pipe clamps