Liebert iCOM
®
Control
85 Liebert
®
CRV
Figure 76 Set alarms parameters screen - Page 4
This screen selects the operation of an active alarm. Each event can be enabled or disabled and can be
set to operate as an alarm, warning or message. The delay is the time the control waits before
reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
Warning / Alarm: Annunciates the buzzer, triggers a monitoring event, shows the event in the
event viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
S234
S235
S236
S237
S238
S239
S240
S241
S242
S243
S244
S245
S246
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
CALL SERVICE 5 ENABLE ALM
HIGH TEMPERATURE 5 ENABLE ALM
HEAT REJ VFD 0 ENABLE ALM
HEAT REJ TVSS 0 ENABLE ALM
CONDENSER 1 FAILURE 0 ENABLE WRN
CUSTOMER INPUT 2 5 ENABLE ALM
CUSTOMER INPUT 3 5 ENABLE ALM
CUSTOMER INPUT 4 5 ENABLE ALM
SET ALARMS (page 4 of 4) UNIT 01