Heatiator C40 Fire Pit User Manual


 
Page 60
Heatilator • Constitution EPA Fireplace • 480-1091H
4/12
INSTALLATION
1. Remove the knockout or cover plate from the top of the
replace and discard it. See Figure 11.2.
2. Cut a 3 in. (76mm) hole in the insulation board as per the
dimensions shown in Figure 11.2
Adapter
Mounting
Plate
Starter Pipe
Knockout
Cut a 3 in. (76mm) hole
in insulation board
3-13/16 in.
(97mm)
3-1/8 in. (79mm)
C
L
Run Length Cut Pipe
20 - 40 ft (6-12m) 2 in. (51mm)*



10 - 20 ft (3 - 6m) 8 in. (203mm)
3 - 10 ft (1 - 3m) No cut needed**
**
3. Determine the necessary length of starter pipe from the
following table and cut as required. See Figure 11.3.
4. The starter pipe is shipped at. After cutting to the required
length, manually roll the pipe together and snap lock into
place. 

Figure 11.2
Figure 11.3
5. Slide the starter pipe into the replace, matching the holes
in the plate to the holes in the replace.
6. Place the Adapter on the Mounting Plate lining up holes.
Using the 4 sheet metal screws included in the kit, secure
the Adapter and Mounting Plate into replace. After secur-
ing to the replace, tape down the Adapter edges to the top
of the replace with aluminum tape to prevent leakage.
7. Determine the location for the air register and fan housing
assembly. Cut a 7-5/8 in. x 13-5/8 in. (143 x 346mm) hole
between framing members (wall studs or oor joists). The
brackets can be rotated 180° and mounted to the back side
of the 2 x 4 if necessary. See Figure 11.6 on page 61.
   





8. Attach enough 6 in. (152mm) B-Vent as required for
your installation to the fan housing. A maximum of (4) 90°
elbows is recommended. Securely twist lock the B-Vent
to the Adapter.
Also screw the B-Vent to the outlet box on the fan housing.
See Figure 11.6 on page 61.
Support duct at intervals of no
greater than 4 ft (1 m) as required by local code.
Figure 11.4
Warning Fire Risk!

       

