Heatiator C40 Fire Pit User Manual


 
Page 58
Heatilator • Constitution EPA Fireplace • 480-1091H
4/12
60 in.
(1524mm)
Mantel
Clearances are
from bottom of
appliance to lower
edge of mantel or
trim
Trim
48 in.
(1219mm)
A combustible mantel may be positioned no lower than 60 in.
(1524mm) from the base of the replace.
The combustible mantel may have a maximum depth of 12 in.
(305mm). Combustible trim pieces that project no more than
3/4 in. (19mm) from the face of the replace can be placed
no closer than 6 in. (152mm) from the side of the decorative
front. See Figure 10.13
Combustible trim must not cover:
the metal surfaces of the replace
where the non-combustible board is placed over the metal
surfaces
the space between the metal face of the replace and framing
members.
Figure 10.13 Mantel Specications
F. Mantel
Refer to page 37 for clearance requirements