Heatilator • Constitution EPA Fireplace • 480-1091H
4/12
Install as per Sections 7 and 8.
You MUST use a chase top in a chase installation. Chase
tops are available from your Heatilator dealer or may be
eld constructed.
Include a turndown and drip edge to prevent water from
seeping into the chase.
Include a 2 in. (51 mm) soldered, welded or spun collar
around pipe opening to keep water out.
Provide a 1/8 in. (3 mm) gap around the ue pipe.
Slope the chase top downward away from the opening.


Caulk all seams to prevent leaks.
Slope Downward
(1/4 in. per foot
minimum)
Turn-down
Drip Edge
Chase
2 in. (51 mm) Collar
on Chase Top
.018 (26 ga) min.
Galvanized
Chase Top
Figure 9.3 Chase Top Construction
Install the chimney sections up through the chase enclo-
sure.
Caulk the overlap seam of any exposed pipe sections
that are located above the roof line to prevent leaks.
Refer to termination cap instructions.







TR344 Round Termination Cap
Storm
Collar
Chimney
Pipe
Chase Top
Termination
Cap
Chase
6 in. (153 mm)
Minimum top of
chase to top of
chimney pipe
Collar
2 in. (51 mm)
Minimum Height
Do NOT
block air holes
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Termination cap pipe and chimney section must be snapped
together to maintain an overlap of 1-1/2 in. (38 mm).
Slip
storm collar
around chimney pipe
before termination
cap pipe is snapped
into the chimney
pipe.
Figure 9.4 Installing a TR344 Round Termination Cap
TR342 Round Telescoping Termination Cap
Storm
Collar
Chimney
Pipe
Chase Top
Termination
Cap
Chase
14 1/2 in. (368 mm)
Maximum
Collar
2 in. (51 mm)
Minimum Height
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Do NOT
block air
holes
3 clip brackets.
Slip over chase collar
and attach with screws
provided.
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)
Assemble
storm collar
around extended
termination cap
pipe
once cap is
installed.
Figure 9.5 Installing a TR342 Round Telescoping Termination
Cap
D. Install Termination Cap
B. Install Fireplace & Chimney
C. Install Chase Top