Heatiator C40 Fire Pit User Manual


 
4/12
Heatilator • Constitution EPA Fireplace • 480-1091H
Page 43
Vertical distances are measured from the base of the re-
place as shown in Figure 8.2
To determine the chimney components needed to complete your
particular installation, follow the steps below:
Determine the total vertical height of the replace installation. This
dimension is measured from the base of the replace assembly
to the point where the smoke exits the termination cap.
Subtract the effective height of the replace assembly from the
overall height of the replace installation (measured from the
base of the replace to the bottom of the termination cap, 13 ft.
(4m).
Refer to Table 8.1 to determine what components must be
selected to complete the replace installation.
Determine the number of ceiling firestops, stabilizers, roof
ashing, etc. required to complete the replace installation.
6 ft (1.8 m) max.
unsupported
run
20 ft (6.10 m) max.
pipe between an
offset & return
Ceiling firestop
35 ft (10.7 m)
max. straight
unsupported
chimney height
14.5 ft (4.42 m) min. height/single offset-return
20 ft. (6.10 m) min. height/double offset-return
50 ft (15.24 m) max. height
6
f
t
(
1.83 m
)
max.
unsupported chimney
above roof
44 in.
(1118 mm)
to top of
standoffs
Figure 8.2 Chimney Requirements
Table 8.1
HEIGHT OF CHIMNEY COMPONENTS  
Chimney Stabilizer
SL3 4-3/4 121
Ceiling Firestops
FS338 0 0
FS339 0 0
FS340 0 0
Offsets/Returns
SL315 13-3/8 340
SL330 15-1/2 394
Roof Flashing
RF370 0 0
RF371 0 0
Chimney Sections*
SL306 4-3/4 121
SL312 10-3/4 273
SL318 16-3/4 425
SL324 22-3/4 578
SL336 34-3/4 883
SL348 46-3/4 1187
* Dimensions reect effective height.


Minimum overall straight height 13 ft 3.96 m
Minimum height with single offset/
return
14.5 ft 4.42 m
Double offset/return minimum height 20 ft 6.1 m
Maximum height 50 ft 15.24 m
Maximum chimney length between an
offset and return
20 ft 6.1 m
Maximum distance between chimney
stabilizers
35 ft 10.67 m
Maximum unsupported chimney
length between the offset and return
6 ft 1.83 m
Maximum unsupported chimney
height above the replace
35 ft 10.67 m
Maximum unsupported chimney
above roof
6 ft 1.83 m










 



A. Chimney Requirements
B. Chimney Termination Requirements