C. FIREPLACE DIMENSIONS
23-1/8"
11-1/8"
9-11/16"
6-1/2"
5-7/8"
1"
Fan Electrical Access,
(right side of fireplace)
See Page 10
TOP VIEW
FRONT VIEW
SIDE VIEW
MINIMUM CLEARANCES TO COMBUSTIBLES
NONCOMBUSTIBLE
DECORATIVE MATERIAL
(2) HX4 MICORE FACTORY
BUILT HEARTH EXTENSION
(Each HX4 = 1/2" (13mm) thick)
HEARTH METAL STRIPS
GAP (SEAL WITH NONCOMBUSTIBLE SEALANT)
UP TO BOTTOM OF FASCIA
6" (152mm)
1" (51mm)
40-5/16"
31-1/8
"
37"
3-1/2"
40"
43-13/16"
Figure 5A - Factory Built Hearth Extension
WITHIN ENCLOSURE AREA:
Appliance to backwall 1” (25mm)
Appliance to sidewall 1” (25mm)
Duct boots to framing 0” (0mm)
Top standoffs to header 0” (0mm”)
EXPOSED SURFACES
Faceplate to sidewall 16” (406mm)
Heat Zone air grills to ceiling 12”(305mm)
HEARTH EXTENSION / FLOOR PROTECTION
1. Fireplace and Hearth Extension are ush on the oor:
Combustible ooring 20” (508mm) in front of and 8” (203mm) to either side of the fuel opening; must be insulated with
non-combustible oor protection with a minimum thickness of 1” (25mm) and (“k” value = 0.43).
2. Fireplace is ush on the oor and Hearth Extension is raised to the bottom of the fascia:
Raised hearth must be constructed of non-combustible materials such as cement block or equivalent material Decorative
combustible ooring on the raised hearth must be 20” (508mm) in front of and 8” (203mm) to either side of the fuel
opening must be insulated with non-combustible floor protection with a minimum thickness of 1-1/2” (38mm) and
(“k” value = 0.43).
3. Fireplace is recessed in the oor to the bottom of the fascia:
Combustible ooring 30” (762mm) in front of and 8” (203mm) to either side of the fuel opening ;must be insulated with
non-combustible oor protection with a minimum thickness of 1” (25mm) and (“k” value = 0.43).
MANTEL
Mantel from base of replace 60” (1524mm)
Maximum mantel width 12” (305mm
CHIMNEY SECTIONS
Chimney sections at any level require a 2” (51mm) minimum
air space clearance between the framing and chimney
section.