Hearth and Home Technologies BIR50 Outdoor Fireplace User Manual


 
480-1081 14 4-03
North Star
EPA Certied Fireplace
ROOM ABOVE
A
TTIC ABOVE
Figure 14A
Installing the Firestop Spacer
CAUTION:
Firestop spacers must be used whenever the
chimney penetrates a ceiling/oor area.
24"
AS8 ATTIC
INSULATION
SHIELD
FS338
FIRESTOP
SPACER
CHIMNEY
IN
SULATION
10-1/2"
14-1/2"
Figure 14B
Installing an Attic Insulation Shield
6. Attic Insulation Shield
An insulation shield should be installed when there is a
possibility of insulation coming into contact with the factory
built chimney system. The insulation shield is installed by
positioning it over the vertical chimney section where it
penetrates a restop spacer. The restop spacer will support
the insulation shield. See Figure 14B.
5. Installing Firestop Spacers
Mark and cut out an opening in the ceiling for the restop
spacer being utilized (14-1/2” x 14-1/2” for an FS338, 14-1/2”
x 18-3/8” for an FS339 and 14-1/2” x 23” for an FS340).
Frame the opening with the same dimension lumber used
in the ceiling joists.
Install the restop spacer.
These restop spacers are designed to provide the minimum
2” air space required around the chimney. In all situations, the
restop spacers are to be nailed to the ceiling joists from the
bottom or replace side, EXCEPT when the space above is
an insulated ceiling or attic space. In this situation, the restop
spacer must be nailed from the top side to prevent loose
insulation from falling into the required 2” air space around the
chimney. See Figure 14A.
7. Double-checking the Chimney Assembly
Continue assembling the chimney sections up through the
restop spacers as needed. While doing so, be aware of the
height and unsupported chimney length limitations that are
given on page 10 under “Chimney Requirements”.
Check each section by pulling up slightly from the top to
ensure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.
NOTE: Wiring for blowers must be done before
framed enclosure is completed. If using a Heat
Zone kit, it also must be installed before enclosure
is complete.