Hearth and Home Technologies BIR50 Outdoor Fireplace User Manual


 
480-1081 12 4-03
North Star
EPA Certied Fireplace
THEN
BUT
MUST BE AT
LEAST 2 FEET
NEVER LESS
THAN 3 FEET
I
F 10
FEET OR
LESS
Figure 12A- Chimney Height
*Dimensions reect effective height.
Table 2
2. Chimney Height Requirements (above roof
line)
a. Major building codes specify a minimum chimney
height above the roof top. These specications are
summarized in what is known as the Ten Foot Rule.
This rule states:
If the horizontal distance from the side of the
chimney to the peak of the roof is 10 feet or less, the
top of the chimney must be at least 2 feet above
the peak of the roof, but never less than 3 feet
in overall height above the highest point where it
passes through the roof.
If the horizontal distance from the side of the
chimney to the peak of the roof is more than 10 feet,
a chimney height reference point is established on
the surface of the roof a distance of 10 feet from the
side of the chimney in a horizontal plane. The top
of the chimney must be at least 2 feet above this
reference point, but never less than 3 feet in height
above the highest point where it passes through the
roof. See Figure 12A.
b. These chimney heights are necessary in the interest
of safety but do not ensure smoke-free operation.
Trees, buildings, adjoining roof lines, adverse wind
conditions, etc. may create a need for a taller
chimney should smoking occur.
3. Number of Sections Required
To determine the chimney components needed to
complete your particular installation, follow the steps
below:
a. Determine the total vertical height of the replace
installation. This dimension is measured from the
base of the replace assembly to the point where
the smoke exits the termination cap.
b. Subtract the effective height of the replace assembly
from the overall height of the replace installation
(measured from the base of the replace to the
bottom of the termination cap).
c. Refer to Table 2 to determine what components must
be selected to complete the replace installation.
d. Determine the number of restop spacers, stabiliz-
ers, roof ashing, etc. required to complete the
replace installation.
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer
SL3 4-3/4”
Firestop Spacers
FS338 0”
FS339 0”
FS340 0”
Offsets/Returns
SL315 13-3/8”
SL330 14-1/2”
Roof Flashing
RF370 0
RF371 0
Chimney Sections*
SL306 4-3/4”
SL312 10-3/4”
SL318 16-3/4”
SL324 22-3/4”
SL336 34-3/4”
SL348 46-3/4”