CDV Series Direct Vent Gas Fireplace
20010175
Top View
Straight Venting
Fig. 12 Rear vent applications.
13"
(330 mm)
Max.




FP1598
Rear Wall Installation
Twist Lock Pipe
STEP 1
Locate vent opening on the wall. To locate hole center
consult with appropriate fireplace dimensions, Page 4.
Frame as shown below.
Combustible Walls
(Fig. 13): Cut a 9³⁄₈”H x 9³⁄₈” W
(240 x 240 mm) hole through the exterior wall and
frame as shown.
Noncombustible Walls
(Fig. 13): Hole opening must
be 7¹⁄₂” (190 mm) in diameter.
VO584-100
Vent Opening
2/99 djt
Vent Opening for Combustible Wall
9³⁄₈
(240 mm)
9³⁄₈
(240 mm)
Fireplace Hearth
Framing
Detail
Opening for Noncombustible Wall
7¹⁄₂
(190 mm)
VO584-100
Fig. 13 Locate vent opening on wall.
STEP 2
Install interior firestop as shown in Figure 14.
STEP 3
Remove telescoping collar from termination.
STEP 4
Bend tab on outer casing up and insert collar onto fire-
place collars. (Fig. 14)



Firestop
FP1600
Fig. 14 Install firestop.
Bend Tab
FP1005
Side View Vent Termination
1/25/00 djt
22”
(559 mm)
C
L
Finished
Wall
Secure with Screw
Vent Termination
Firestop
FP1005a
Fig. 15 Side view of final unit location.
STEP 5
Twist the termination collar so it locks onto fireplace col
-
lars. Run screw through tab to keep collar from turning.
(Fig. 15)
STEP 6
Slide fireplace into position.
STEP 7
From the outside of the house, slide the termination
onto the collars.
STEP 8
Secure the termination to the house with the four (4)
screws provided.