Under extreme vent confi gurations, allow several minutes
(5-15) for the fl ame to stabilize after ignition.
Provide adequate ventilation and combustion air.
Provide adequate accessibility clearance for servicing and
operating the fi replace. Never obstruct the front opening of
the fi replace.
Objects placed in front of the fi replace must be kept a
minimum of 48” from the front face of the unit.
* The fi rst 2 feet of outer 7 inch diameter vent pipe from the appliance
must be wrapped in the 1” thick insulation sleeve (supplied).
There must be a 1” air gap in addition to the insulation. Thereafter
a 1” clearance all around the vent pipe is acceptable.
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN
TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
Maximum input is 26,000 BTU/hr for both natural gas and
propane. When the fi replace is installed at elevations above
4,500ft, and in the absence of specifi c recommendations
from the local authority having jurisdiction, the certifi ed high
altitude input rating shall be reduced at the rate of 4% for each
additional 1,000ft. Maximum output for natural gas is 16150
BTU/hr at an effi ciency of 62%; and 16150 BTU/hr for propane
at an effi ciency of 62%. Minimum inlet gas supply pressure is
4.5 inches water column for natural gas and 11 inches water
column for propane. Maximum inlet gas pressure is 7 inches
water column for natural gas and 13 inches water column for
propane. Manifold pressure under fl ow conditions is 3.5 inches
water column for natural gas and 10 inches water column for
propane.
FIGURE 1
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SER-
VICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it
is important to know the specifi cs that apply to your area,
for example: in Massachusetts State:
• The fi replace damper must be removed or welded in the
open position prior to installation of a fi replace insert or
gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
• A carbon monoxide detector is required in all rooms containing
gas fi red appliances.
• WARNING: This product must be installed by a licensed
plumber or gas fi tter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install to the current CAN/CGA
-B149 Installation Code in Canada or to the National Fuel
Gas Code, ANSI Z223.1, and NFPA 54 in the United States.
Suitable for mobile home installation if installed in accordance
with the current standard CAN/CSA Z240MH Series, for gas
equipped mobile homes, in Canada or ANSI Z223.1 and NFPA
54 in the United States.
The fi replace and its individual shutoff valve must be discon-
nected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa). The fi replace must be isolated from the gas supply
piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fi replace is installed directly on carpeting, vinyl tile
or other combustible material other than wood fl ooring, the
replace shall be installed on a metal or wood panel extending
the full width and depth.
The optional heat circulating blower is supplied with a cord. If
installed, the junction box must be electrically connected and
grounded in accordance with local codes. In the absence of
local codes, use the current CSA C22.1 CANADIAN ELEC-
TRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL
ELECTRICAL CODE in the United States.
Purge all gas lines with the glass door of the fi replace open.
Assure that a continuous gas fl ow is at the burner before
closing the door.
GENERAL INSTRUCTIONS
GENERAL INFORMATION
22
1
/8"
21"
4" DIA.
7" DIA.
17
3
/4"
13
7
/8"
28"
14"
7
/8"
46"
58"
2"
8
7
/8"
28"
37
5
/8"
24"
5"
Minimum clearance to combustible construction from
replace and vent surfaces:
fireplace framing - 0” to stand-offs (top, rear and sides)
replace fi nishing - 4” from the sides of fi rebox opening
21
3
/
4
” to top of fi replace opening.
vent pipe - 2 inches*
recessed depth - 22
1
/
4
inches