39
5. The pilot and main
burner extinguish
while in operation
A. Inner vent pipe
leaking exhaust
gases back into
system
Check for flue product leak. Replace defective pipe section.
B. Horizontal vent
improperly pitched
Check horizontal-venting piping is running upward 1/4” per
foot.
C. Improper vent cap
installation
Check for proper and freedom from debris or blockage.
6. Glass Soots A. Flame
impingement on
logs
Install log set per the instructions
Inspect the injector and air intake area. Make sure this area
does not have any blockage from debris and clean.
Check gas supply
7. Flame burn blue
and lifts off burner
(ghosting)
A. Insufficient oxygen
being supplied
Ensure that the vent cap is installed properly and free of
debris. Ensure that the vent system joints are tight and have no
leaks.
Ensure that no debris has been blocking the inner air intake at
the bottom back of the combustion chamber.
Ensure that the glass is properly secure and latch.