Emerson 8712E Grill Accessory User Manual


 
Quick Installation Guide
00825-0100-4664, Rev BB
January 2013
Rosemount 8712 / 8700 Series
27
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Eden Prairie, Minnesota, USA
Fisher-Rosemount Technologias de Flujo, S.A. de C.V. — Chihuahua Mexico
Emerson Process Management Flow — Ede, The Netherlands
Asia Flow Technology Center — Nanjing, China
European Directive Information
The EC declaration of conformity can be found on page 31. The most recent revision can be found
at www.rosemount.com.
Type n protection type in accordance with EN 50021
Closing of entries in the device must be carried out using the appropriate EExe or EExn
metal cable gland and metal blanking plug or any appropriate ATEX approved cable
gland and blanking plug with IP66 rating certified by an EU approved certification body.
CE Marking
Complies with EN 61326-1: 2006
Complies with Essential Health and Safety Requirements:
EN 60079-15: 2003
International Certificates
C-Tick Marking
Rosemount Inc. complies with the following IEC Requirements:
IEC 60079-0: 2004
IEC 60079-15: 2005-03
Hazardous Locations Certifications
North American Certifications
Factory Mutual (FM)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 40 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G
(T4 at 40 °C)
Hazardous Locations; Enclosure Type 4X, IP66
N5 Non-incendive for Class I, Division 2,
Groups A, B, C, and D flammable fluids
(T4 at 40 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G
(T4 at 40 °C)
Hazardous Locations; Enclosure Type 4X, IP66
Requires sensors with N5 Approval
4664RevBBQIG.fm Page 27 Friday, January 11, 2013 6:13 PM